Users Guide
USA
MADE IN
www.omega.com
iSeries info:
www.omega.com/specs/iseries
Temperature & Process Controller Manual
CNi8, CNi8C, CNi8DH, CNi8DV,
CNi16, CNi16D, CNi32
Shop on line at
Zobrazit stránku 0
1 2 3 4 5 6 ... 71 72

Shrnutí obsahu

Strany 1 - User’s Guide

User’s GuideUSAMADE INwww.omega.come-mail: [email protected] info:www.omega.com/specs/iseriesTemperature & Process Controller ManualCNi8, CNi8

Strany 2 - Servicing Europe:

2.2 Rear Panel ConnectionsThe rear panel connections are shown in Figures 2.2 and 2.3.Figure 2.2 Rear Panel Power and Output ConnectionsFigure 2.3 Rea

Strany 3 - TABLE OF CONTENTS

2.3 Electrical Installation2.3.1 Power ConnectionsCaution: Do not connect power to your device until you have completed allinput and output connection

Strany 4 - LIST OF TABLES:

2.3.2 ThermocoupleThe figure below shows the wiring hookup for any thermocouple type. Forexample, for Type K hookup, connect the yellow wire to the &q

Strany 5 - NOTES, WARNINGS and CAUTIONS

92.3.3 Two/Three/Four-Wire RTDThe figures below show the input connections and input connector jumpers(shown in bold lines) required to hookup a 2-, 3

Strany 6 - 1.1 Description

102.3.4 Process CurrentThe figure below shows the wiring hookup for Process Current 0 – 20 mA.Figure 2.7 Process Current Wiring Hookup(Internal and Ex

Strany 7 - EMC Considerations

112.3.6 Wiring OutputsThis meter has two factory installed outputs. The SPDT Mechanical Relay, SPSTSolid State Relay, Pulse and Analog Output Connecti

Strany 8 - 1.3 Before You Begin

This device may have a programmable communication output. The RS-232 and RS-485 Output Connection are shown below.External RS-232 connections are not

Strany 9 - 2.1 Front Panel

2.3.7 Dual Display Color SetupThe dual display option allows the user to change the color of the upper andlower displays. To change the color of the u

Strany 10 - 2.2 Rear Panel Connections

14PART 3OPERATION: Configuration Mode3.1 IntroductionThe instrument has two different modes of operation. The first, Run Mode, isused to display value

Strany 11 - 2.3.1 Power Connections

153.2 Menu ConfigurationIt is required that you put the controller in the Standby Mode for anyconfiguration change other than Setpoints & Alarms.F

Strany 12 - 2.3.2 Thermocouple

It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI regulations that apply. OMEGA is constantly pursuing certification of its pr

Strany 13 - 500 ohm Wiring Hookup

163.2.1 ID NumberSEE ID MENU SELECTION IN CONFIGURATION SECTION FORENABLE/DISABLE OR CHANGE ID CODE. If ID Code is Disabled or set as Default (0000) t

Strany 14

173.2.2 Set PointsSETPOINT 1:Press a 1) Press a, if necessary until SP1prompt appears.Press d 2) Display shows previous value of “Setpoint 1”.Press b

Strany 15 - Figure 2.9

183.2.3 Configuration MenuFigure 3.2 Flow Chart for Configuration MenuEnter Configuration Menu:Press a 1) Press a, if necessary, until CNFGprompt appe

Strany 16

19Input Type (Thermocouple)ENTER INPUT TYPE MENU:Press a 1) Press a, if necessary, until CNFGprompt appears.Press d 2) Display advances to INPTInput M

Strany 17

20Input Type (RTD)ENTER INPUT TYPE MENU:Press a 1) Press a, if necessary, until CNFGprompt appears.Press d 2) Display advances to INPTInput Menu.Press

Strany 18 - 3.1 Introduction

21Input Type (Process)ENTER INPUT TYPE MENU:Press a 1) Press a, if necessary, until CNFGprompt appears.Press d 2) Display advances to INPTInput Menu.P

Strany 19 - 3.2 Menu Configuration

22ENTER READING CONFIGURATION MENU:Press a1) Press a, if necessary, until CNFGprompt appears.Press d2) Display advances to INPTInput Menu.Press a3) Di

Strany 20 - 3.2.1 ID Number

23Reading Configuration (If Process was selected)INPUT/READING (SCALE AND OFFSET) SUBMENU:Input Voltage or Current can be converted or scaled into val

Strany 21 - 3.2.2 Set Points

24Conversion number is a coefficient of conversion between input valuesand real full display range (10000 counts shown as 9999). See Table 3.2below fo

Strany 22 - 3.2.4 Input Type Menu

253.2.6 Alarm 1This unit is equipped with two physical outputs that can only be configured asfollows: Alarm 1 & Alarm 2, Alarm 1 & Output 2, O

Strany 23 - Input Type (Thermocouple)

TABLE OF CONTENTSPart 1: Introduction...21.1 Description ...

Strany 24 - Input Type (RTD)

26ALARM 1 ENABLE/DISABLE SUBMENU:Press b 5) Scroll though the available selection until ENBLdisplays touse Alarm 1.Press d 6) Display shows STRDstor

Strany 25 - 3.2.5 Reading Configuration

27CONTACT CLOSURE SUBMENU:Press d11) Display flashes previous selection. Press b to N.ç. NormallyClosed or N.o. Normally Open.Press d12) Display sho

Strany 26

28ALARM ENABLE/DISABLE AT POWER ON:Press d15) Display flashes previous selection. Press bto ENBLenableor DSBLdisable.Press d 16)Display shows STRDst

Strany 27

293.2.7 Analog Output (Retransmission)Analog Output can be configured as Retransmission or Control outputs.In this section we will discuss Retransmiss

Strany 28 - Table 3.2 Conversion Table

30ANALOG OUTPUT ENABLE/DISABLE SUBMENU:Press b5) Scroll though the available selection until ENBLdisplays touse Analog Output Retransmission (output p

Strany 29 - 3.2.6 Alarm 1

31Accuracy of Analog Output board is +/-1% of FS (Full Scale) when followingconditions are satisfied:1. The input is not scaled below 1% of Input FS (

Strany 30

323.2.8 Alarm 2This unit is equipped with two physical outputs that can only be configured asfollows: Alarm 1 & Alarm 2, Alarm 1 & Output 2, O

Strany 31

333.2.9 Loop Break Time/Field CalibrationFigure 3.8 Flow Chart for Loop Break Time/Field CalibrationENTER LOOP BREAK TIME MENU:Press a1) Press a, if

Strany 32

343.2.9 Loop Break Time/Field Calibration (continued)Reading Offset Adjust allows the user to fine tune a minor error of the transducer,however some a

Strany 33

353.2.10 Output 1Alarm 1 and Output 1 or Analog Output (Retransmission) share the same contactson the rear panel connector. If Alarm 1 or Analog Outpu

Strany 34

LIST OF FIGURES:Figure 2.1 Front Panel Display...5Figure 2.2 Rear Panel Pow

Strany 35

36ENTER OUTPUT 1 MENU:Press a1) Press a, if necessary, until CNFGprompt appears.Press d2) Display advances to INPTInput Menu.Press a3) Press a, if

Strany 36 - 3.2.8 Alarm 2

37MAXIMUM/PERCENT HIGH SUBMENU:Specify in percent, the maximum value (99) for control output. If the output isanalog proportional (Current or Voltage)

Strany 37

38ACTION TYPE SUBMENU:The error that results from the measurement of the Process Variable may bepositive or negative since it may be greater or smalle

Strany 38

39If Anti Integral (Anti Windup) Submenu “Enabled”, this feature allows the error term outside the proportional band to be calculated andaccumulated f

Strany 39 - 3.2.10 Output 1

40RESET SETUP SUBMENU:Press d33) Display flashes 1stdigit of the previous IRESTReset value.Press b& c34) Press band cbuttons to enter a new “Res

Strany 40

41DAMPING FACTOR SUBMENU:Press d42) Display flashes the previous “Damping Factor” selection.Press b43) Scroll through the available selections: 0000

Strany 41

423.2.11 Output 2Output 2 and Alarm 2 share the same contacts on the rear panel connector. IfAlarm 2 is Enabled, Output 2 is automatically Disabled.Fi

Strany 42

43ACTION TYPE SUBMENU:The error that results from the measurement of the Process Variable may bepositive or negative since it may be greater or smalle

Strany 43

44CYCLE TIME SUBMENU:Press d15) Display flashes 1stdigit of the previous “Cycle Time” value.Press b& c16) Press band cbuttons to enter a new “Cy

Strany 44

453.2.12 Ramp & SoakAlarm must be DISABLED if Ramp is ENABLED.Figure 3.11 Flow Chart for Ramp and SoakENTER RAMP AND SOAK MENU:Press a1) Press a,

Strany 45

NOTES, WARNINGS and CAUTIONSInformation that is especially important to note is identified by following labels:• NOTE • WARNING or CAUTION• IMPORTANT•

Strany 46 - 3.2.11 Output 2

46SOAK ENABLE/DISABLE SUBMENU:Press d7) Display flashes ENBLor DSBL.Press b8) Scroll through the available selections: “Enable” or “Disable”.Press

Strany 47

473.2.13 ID CODEFigure 3.12 Flow Chart for ID CodeENTER ID CODE MENU:Press a1) Press a, if necessary, until CNFGprompt appears.Press d 2) Display ad

Strany 48

48ENTERING OR CHANGING YOUR (DEFAULT) ID CODE:Enter IDmenu (Repeat steps from 1 to 3).Press d10) Display advances to CH.IDChange ID Code Submenu.Pres

Strany 49 - 3.2.12 Ramp & Soak

493.2.14 COMMUNICATION OPTIONPurchasing the controller with Serial Communications permits an instrument to be configuredor monitored from an IBM PC co

Strany 50

50ENTER COMMUNICATION OPTION MENU:Press a1) Press a, if necessary, until CNFGprompt appears.Press d2) Display advances to INPTInput Menu.Press a3)

Strany 51 - 3.2.13 ID CODE

51STOP BIT SUBMENU:Press d15) Display flashes previous selection for “Stop Bit”.Press b16) Scroll through the available selections: 1-BIT, 2-BIT.Pre

Strany 52

52Press d25) Display flashes previous selection for “Echo”.Press b26) Scroll through the available selections: NO, YES.Press d27) Display flashes STRD

Strany 53 - 3.2.14 COMMUNICATION OPTION

53DATA FORMAT SUBMENU:Preformatted data can be sent automatically or upon request from the controller.Use the Data Format Submenus to determine what d

Strany 54

54TEMPERATURE UNIT SUBMENU:Includes a byte in the data string to indicate whether reading is in Celsius orFahrenheit.Press d50) Display flashes previ

Strany 55

553.2.15 DISPLAY COLOR SELECTIONThis submenu allows the user to select the color of the display.Figure 3.14 Flow Chart for Display Color SelectionENT

Strany 56

PART 1INTRODUCTION1.1 DescriptionThis device can be purchased as monitor (read process value only) or asa controller.• The iSeries controller offers u

Strany 57

56ALARM 2 DISPLAY COLOR SUBMENU:Press d11) Display flashes previous selection for “Alarm 2 Color Display”.Press b12) Scroll through the available se

Strany 58

57Example 3:Output 1 = Analog Output (Alarm 1 disabled), Setpoint 1 = 300,Output 2 = Relay, Setpoint 2 = 200Alarm 1 & 2 Setup: Deviation, Band, “A

Strany 59

58PART 4SPECIFICATIONSAccuracy±0.5°C temp; 0.03% reading processResolution1°/0.1°; 10 µV processTemperature Stability1) RTD: 0.04°C/°C2) TC @ 25°C (77

Strany 60

59ModesTime and Amplitude ProportionalControl Modes; selectable Manual orAuto PID, Proportional, Proportionalwith Integral, Proportional withDerivativ

Strany 61

60EXCITATION(optional in place of Communication)24 Vdc @ 25 mANot available for Low Power OptionINSULATIONPower to Input/Output2300 Vac per 1 min. tes

Strany 62 - SPECIFICATIONS

61JKTERSBCNLRTDRTDTable 4.1 Input PropertiesTC Input Type Range Accuracy*Iron-Constantan -210 to 760°C 0.4°C-346 to 1400°F 0.7°F-270 to -160°C 1.0°CCH

Strany 63

62PART 5FACTORY PRESET VALUESTable 5.1 Factory preset valueMENU ITEMS FACTORY PRESET VALUES NOTESSet Point 1 (SP1) 000.0Set Point 2 (SP2) 000.0Input:I

Strany 64 - (Low Voltage/Power Option)

63MENU ITEMS FACTORY PRESET VALUES NOTESRamp & Soak (RAMP):Ramp (RAMP) Disable (DSBL)Soak (SOAK) Disable (DSBL)Ramp Value (RAMP) 00:00Soak Value (

Strany 65 - Table 4.1 Input Properties

64PART 6CE APPROVALS INFORMATIONThis product conforms to the EMC directive 89/336/EEC amended by93/68/EEC, and with the European Low Voltage Directive

Strany 67

1.2 Safety ConsiderationsThis device is marked with the international caution symbol. It is importantto read this manual before installing or commissi

Strany 69

WARRANTY/DISCLAIMEROMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of one (1) yearfrom the

Strany 70

Where Do I Find Everything I Need for Process Measurement and Control? OMEGA…Of Course!Shop on line at www.omega.comTEMPERATUREThermocouple, RTD &am

Strany 71 - RETURN REQUESTS/INQUIRIES

1.3 Before You BeginInspecting Your Shipment:Remove the packing slip and verify that you have received everythinglisted. Inspect the container and equ

Strany 72 - Shop on line at www.omega.com

PART 2SETUP2.1 Front PanelFigure 2.1 Front Panel DisplayTable 2.1 Front Panel Annunciators1 Output 1/Setpoint 1/ Alarm 1 indicator2 Output 2/Setpoint